EML-6014 Exit Sign Luminaire General Specifications Light Source: LED 1W, 50,000 hours operation, 6000K color temperature Viewing Distance: 30 meters Housing: White plastic Protection Class: Class II Dimensions: 337mm x 170mm x 215mm Cable Connection: Maximum 2.5mm² cross-section solid or sleeved twisted wire Operating Mode: Non-maintained / Maintained Protection Rating: IP65 Certificates: CE, UL Warranty: 5-year replacement warranty Ambient Temperature Range: 0°C < Ta < 45°C Made in Hungary brand name EML or equivalent.   IEC 60598-1, IEC 60598-2-22, DIN 4844 and EN 1838. EMC protection acc. To EN 550 15. EN 61000-3-2, EN 61347-1, EN 61347 2-13 and EN 61547. Sub-types and Specific Parameters EML-6014 SLAVE CON MB Type: Conventional with self-contained battery Test: Automatic (monthly/annual cycles) Mounting: Ceiling Mains Voltage: AC 120-240V, 50/60Hz Battery: Ni-Mh 600mAh (1-3 hours), charging time up to 24 hours Input Current: 0.032A EML-6014 SLAVE CON CB ACAC Type: Conventional exit light for central battery systems Compatibility: AC/AC line-monitored central battery systems Mounting: Ceiling Mains Voltage: AC 120-240V, 50/60Hz (standby and emergency) Input Current: 0.015A EML-6014 SLAVE CON CB ACDC Type: Conventional exit light for central battery systems Compatibility: AC/DC line-monitored central battery systems Mounting: Ceiling Mains Voltage: AC 120-240V, 50/60Hz (standby), DC 120-240V (emergency) Input Current: 0.015A EML-6014 SLAVE CB ACDC Type: Addressable exit light for AC/DC central battery systems Addressing: Automatic, based on unique factory identification number Communication: Compatible only with CBS-230 AC/DC systems Mounting: Ceiling Mains Voltage: AC/DC 120-240V, 50/60Hz Input Current: 0.015A EML-6014 SLAVE CB 24V Type: Addressable exit light for central battery systems Addressing: Automatic, based on unique factory identification number Communication: Compatible only with EML 24V CB panels Mounting: Ceiling Mains Voltage: DC 24-32V Input Current: 0.08A EML-6014 SLAVE CB Type: Addressable exit light for central battery systems Addressing: Automatic, based on unique factory identification number Communication: Compatible only with EML 600 CB panels Mounting: Ceiling Mains Voltage: AC 120-240V, 50/60Hz Input Current: 0.015A EML-6014 SLAVE MB Type: Addressable exit light with self-contained battery Addressing: Automatic, based on unique factory identification number Communication: Compatible only with EML MB panels Mounting: Ceiling Mains Voltage: AC 120-240V, 50/60Hz Battery: Ni-Mh 600mAh (1-3 hours), charging time up to 24 hours Input Current: 0.032A EML-6014 SLAVE RF MB Type: Wireless addressable with self-contained battery Addressing: Automatic, based on unique factory identification number Communication: Wireless mesh network (868MHz signal) with EML RF MB panels Wireless Coverage: Up to 300 meters in open space Mounting: Ceiling Mains Voltage: AC 120-240V, 50/60Hz Battery: Ni-Mh 600mAh (1-3 hours), charging time up to 24 hours Input Current: 0.032A